The
FPA-12/066F is a PD free AC hipot test set provides continuously adjustable output voltages for overvoltage withstand testing of the following:
- Motor windings
- Generator windings
- Bus duct switchgear
- Circuit breakers
- Reclosers
- Vacuum bottles
- Hot sticks
- Other high voltage insulation requiring AC
Features:
- Continuously adjustable output voltage
- Adjustable overload, 10-110% of rated output current
- Fixed 120% primary overload
- Zero start and external interlock provision
- Keyed EMERGENCY OFF pushbutton
- Top mounted safety lights indicating POWER ON and HIGH VOLTAGE ON conditions
- Secondary connected analog voltmeter, TWO range scale
- Triple range analog current meter
- Dual full kVA output 0-12 kV AC, 500 mA, and 0-6 kV AC, 1000 mA
- Guard/ground return mode switch
- Burn reactor with ON/OFF switch
- One-piece mobile design in heavy-duty hand truck type cabinet (215 lbs.)
- Transit protected meters prevent meter damage between test sites
| INPUT: |
230 V, 50/60 Hz, 30 A, single phase |
| OUTPUT: |
0-6 kV AC, 6 kVA resistive load (1000 mA)
0-12 kV AC, 6 kVA resistive load (500 mA) |
| DUTY: |
6 kVA: 1 hour ON, 1 hour OFF
5 kVA: continuous |
| DISTORTION: |
<5% |
| METER ACCURACY: |
2% FS Accuracy |
| VOLTMETER: |
3.5”, scaled 0-3/6/12 kV AC (RMS) |
| CURRENT METER: |
3.5″, scaled 0-250/500/1000 mA AC |
| DISTORTION: |
Less than 5% |
| SIZE & WEIGHT:
(W X D X H) |
23 x 23.5 x 46 in., 215 lb.
58 x 60 x 117 cm, 98 kg |
| OUTPUT TERMINATION: |
15 ft. long shielded cable |